• Pcec02 4-20mA Analog Output Conductivity Controller
  • Pcec02 4-20mA Analog Output Conductivity Controller
  • Pcec02 4-20mA Analog Output Conductivity Controller
  • Pcec02 4-20mA Analog Output Conductivity Controller
  • Pcec02 4-20mA Analog Output Conductivity Controller
  • Pcec02 4-20mA Analog Output Conductivity Controller

Pcec02 4-20mA Analog Output Conductivity Controller

After-sales Service: 2years
Warranty: 18months
Display: LCD
Appliance: Conductivity Controller
Portable: Non Portable
Certification: CE
Customization:
Diamond Member Since 2010

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
PCEC02
Type
Conductivity Meter
Measuring Range
0.00us-2000ms
Accuracy
±1%F.S.
Temp. Compensation
1mm or 0.1%Fs
Temp. Range
PT 1000/Ntc30K
Temp. Resolution
-10.0 to +130.0ºC
Temp. Accuracy
0.1ºC
Cell Constant
±0.2ºC
Storage Temp.
0 to +70ºC
Waterproof Grade
IP65
Power Supply
From 90 to 260 VAC, Power Consumption < 7 Watts
Transport Package
Carton
Trademark
WTsensor
Origin
China
Production Capacity
1000 Pieces

Product Description

PCEC02 Conductivity controller

Pcec02 4-20mA Analog Output Conductivity Controller
Features
Easy operation
NEMA enclosure for field mounting and panel mounting
Automatically Temperature Compensation
Directly switchable to EC or TDS
Large LC D display with background lighting
EC or TDS sensors can be connected thanks to the sensor supply integrated in the output
Using the setup program: user-friendly programming
Data logging capacity
4-20mA analog output
RS485 communication 

Product overview  

The PCEC02 is used in industrial measuring of the temperature, conductivity, Resistivity, salinity and total dissolved solids,
such as waste-water treatment, environmental monitoring, pure water, sea farming, food production process, etc. The instrument
can be panel, wall or pipe mounted. The instrument provides two current outputs. The maximum load is 500Ω. The instrument
provides 3 relays. It can pass though a maximum of 5A/250VAC or 5A/30VDC.

 
Performance parameters
Functions EC TDS
Measuring range 0.00uS-2000mS   0-133000 ppm
Resolution 0.01/0.1/1 1
Accuracy ±1%F.S. ±1%F.S.
Temp. compensation 1mm or 0.1%FS
Temp. range Pt 1000/NTC30K
Temp. compensation range -10.0 to +130.0ºC
Temp. resolution   -10.0 to +130.0ºC
Temp. accuracy 0.1ºC
Cell constant   ±0.2ºC
Ambient temperature range 0.001 to 20.000
Storage temp. 0 to +70ºC
Display -20 to +70ºC
EC current output1 Isolated, 4 to 20mA output , max. load 500Ω
Temp. current output 2 Isolated, 4 to 20mA output , max. load 500Ω
Current output accuracy ±0.05 mA
RS485 Mod bus RTU protocol
Baud rate 9600/19200/38400
Maximum relay
contacts capacity
5A/250VAC,5A/30VDC
Cleaning setting ON: 1 to 1000 seconds, OFF: 0.1 to 1000.0 hours
One multi-function relay clean/period alarm/error alarm
Relay delay 0-120 seconds
Data logging capacity 500,000
Language selection English/traditional Chinese/simplified Chinese
Waterproof grade IP65
Power supply From 90 to 260 VAC, power consumption < 7 Watts
Installation panel/wall/pipe installation
Weight 144 series:0.85Kg
 
Dimension
144 series: The instrument can be panel, wall or pipe mounted installation. Panel Installation: Make a 138x138 mm square cutout and insert the instrument. Screw in the fixed block with the screws and fixed bar.
Pcec02 4-20mA Analog Output Conductivity Controller                                                                        Installation figure
Wiring
Pcec02 4-20mA Analog Output Conductivity Controller
Display
Pcec02 4-20mA Analog Output Conductivity Controller
1.Date and time
2.Main display
3.Unit
4.Temperature and unit
5.First current output
6.Second current output
7.Measurement status and Error indicator, there is no display if meter is in keeping mode
8.Count down timer: cycle time/clean time, it also displays the "delay" when relay3 has a delay enabled.
9.Temp. compensation: auto(ATC) or manual(MTC)
10.Relay indicator


Note: If the EC readings are over the range, it will display 99.99/999.9/9999 If the temperature readings are under or over the range, it will display -99.9/999.9.

About us:
Pcec02 4-20mA Analog Output Conductivity Controller
Pcec02 4-20mA Analog Output Conductivity Controller
Pcec02 4-20mA Analog Output Conductivity Controller
Certifications:
Pcec02 4-20mA Analog Output Conductivity Controller
FAQ:
1.    Q: Are you manufacturer or trading company?
        A: We are manufacturer which focuses on pressure sensor for 33 years.
2.    Q: What international certificates do you have?
        A: ISO9001, CE, RoHS Certificated.
3.    Q: What is your production capacity?
        A: We produced 1500000 pieces pressure sensor in year 2017.
4.    Q: What is the lead time of your product?
        A: Stocks are available for some products. The typical lead time is 8~14 working days for product without customization. 
       Note: lead time may vary base on different products. Please contact us for detailed lead time. 
5.    Q: What is the warranty of your products?
       A: Our warranty time is 18 months after shipment.
6.    Q: Do you provide customized products?
       A: Yes, we can laser mark your logo, model and product information according to your requirement. We provide OEM and ODM service.
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now