Customization: | Available |
---|---|
Type: | Head Mounted Temperature Transmitter |
Measuring Medium: | Temperature |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input | |
Input signal | Resistance temperature detector(RTD), thermocouple (TC), and linear resistance. |
Cold-junction compensation temperature scope | -20~60ºC |
Compensation precision | ±1ºC |
Output | |
Output signal | 4-20mA |
Load resistance | RL≤(Ue-12)/0.021 |
Output current of upper and lower limit overflow alarm |
IH=21mA,IL=3.8mA |
Power supply | |
Supply voltage | DC12-40V |
Other parameters | |
Temperature drift | 0.02%FS/ºC (Standard) |
0.0075%FS/ºC (Isolated) | |
Response time | Reach to 90% of the final value for 1s |
Used environmental temperature | -40~80ºC |
Storage temperature | -40~100ºC |
Aseismicity | 4g/2~150Hz |
Installation angle | Unlimited |
Installation area | B-type top cassette installation |
Electromagnetic compatibility | Conform to GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Isolated type | |
Insulation strength (between input and output) | 1500Vrms (1 min, without spark) |
Insulation resistance (between input and output) | ≥100MΩ(under the 500 VDC) |
Model | Type | Measurement scope |
Minimum measurement scope |
Scale range | Conversion accuracy |
Resistance temperature detector (RTD) | Pt100 | -200.0~850.0ºC | 10ºC | ≤100ºC | 0.20% |
>100ºC | 0.10% | ||||
Cu50 | -50.0~150.0ºC | 10ºC | ≤100ºC | 0.20% | |
>100ºC | 0.10% | ||||
Thermocouple (TC) | B | 400~1800ºC | 500ºC | ≤300ºC | 0.20% |
>300ºC | 0.10% | ||||
E | -100~1000ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
J | -100~1200ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
K | -180~1372ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
N | -180~1300ºC | 50ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
R | -50~1768ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
S | -50~1768ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
T | -200~400ºC | 50ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
Wre3-25 | 0~2315ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
Wre5-26 | 0~2310ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% |
Model | Type | Measurement scope |
Minimum measurement scope |
Scale range | Conversion accuracy |
Resistance temperature detector (RTD) | Pt100 | -200.0~850.0ºC | 20ºC | ≤100ºC | 0.20% |
>100ºC | 0.10% | ||||
Cu50 | -50.0~150.0ºC | 20ºC | ≤100ºC | 0.20% | |
>100ºC | 0.10% | ||||
Thermocouple (TC) | B | 400~1800ºC | 500ºC | ≤300ºC | 0.20% |
>300ºC | 0.10% | ||||
E | -100~1000ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
J | -100~1200ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
K | -180~1372ºC | 50ºC | ≤300ºC | 0.20% | |
>300ºC | 0.10% | ||||
N | -180~1300ºC | 50ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
R | -50~1768ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
S | -50~1768ºC | 500ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% | ||||
T | -200~400ºC | 50ºC | ≤500ºC | 0.20% | |
>500ºC | 0.10% |