| Customization: | Available |
|---|---|
| Type: | Head Mounted Temperature Transmitter |
| Measuring Medium: | Temperature |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Technical Parameters | |
| Input signal | Resistance temperature detector (RTD), Thermocouple (TC) |
| Cold-junction compensation temperature scope | -20ºC~60ºC |
| Compensation precision | ±1ºC |
| Output signal | 4-20mA |
| Load resistance | RL≤(Ue-12)/0.021 |
| Output current of upper & lower limit overflow alarm | IH=21mA, IL=3.8mA |
| Supply voltage | DC12-40V |
| Temperature drift | 0.0075%FS/ºC |
| Response time | 1s (up to 90% of the final value ) |
| Used environmental temperature | -40~80ºC |
| Storage temperature | -40~100ºC |
| Insulation strength (between input and output) | 1500Vrms (1 min, without spark) |
| Insulation resistance (between input and output) | ≥100MΩ(under the 500 VDC) |
| Vibration resistance | 4g/2 -150Hz |
| Installation angle | Unlimited |
| Installation area | B-type top cassette installation |
| Electromagnetic compatibility | Conform to GB/T18268 industrial equipment application requirements (IEC 61326-1) |
| Input Type and Transmission Accuracy | ||||
| Model | Type | Measurement scope | Minimum measurement scope | Conversion accuracy |
| Resistance Temperature detector (RTD) |
Pt100 | -200~850ºC | 20ºC | ±0.1%range Or±0.2ºC |
| Cu50 | -50~150ºC | 20ºC | ±0.1%range Or±0.2ºC | |
| Thermocouple (TC) | B | 100~1820ºC | 500ºC | ±0.1%range Or±1.5ºC |
| E | -100~1000ºC | 50ºC | ±0.1%range Or±0.5ºC | |
| J | -100~1200ºC | 50ºC | ±0.1%range Or±0.5ºC | |
| K | -180~1372ºC | 50ºC | ±0.1%range Or±0.5ºC | |
| N | -180~1300ºC | 50ºC | ±0.1%range Or±0.5ºC | |
| R | -50~1768ºC | 500ºC | ±0.1%range Or±1.5ºC | |
| S | -50~1768ºC | 500ºC | ±0.1%range Or±1.5ºC | |
| T | -200~400ºC | 50ºC | ±0.1%range Or±0.5ºC | |