Performance parameters | |
Display | 3.5-inch TFT true-color LCD display, resolution 320*240, high-definition LED backlight |
Dimensions | Dimensions: 96mm×96mm×100mm Hole size: 92mm×92mm |
Mounting panel thickness | 1.5mm~6.0mm |
Weight | 0.37kg |
Power supply | (85~264)VAC, (47~63)Hz (optional 24VDC power supply) |
Internal storage | 64M Bytes Flash (optional 96M, 128M) |
External dump | Support U disk (standard USB2.0 communication interface) |
Maximum power consumption | 10W |
Relative humidity | (10~85)% (no condensation) |
Operating temperature | (0~50)ºC |
Transport and storage conditions | Temperature(-20~60)ºC Relative humidity (5~95)% (no condensation) |
Power distribution specification | 150mA, 24 VDC |
Power down protection | All data are stored in Flash memory to ensure that all historical data and configuration parameters will not be lost due to power failure. The real-time clock is powered by an internal battery after power failure. |
Alarm output | Up to 4 channels, relays are normally open contacts, contact capacity 2A /250VAC (resistive load) |
Communication interface | 1 way RS-485 communication interface |
Protocol | Using Modbus communication protocol |
The sampling period | 1s |
Input Signal | |||
DC Voltage/Current Input | |||
Signal type | Maximum allowable error (%FS) | ||
(1~5)V | ±0.1 | ||
(0~10)V | |||
(0~5)V | |||
(4~20)mA | |||
(0~20)mA | |||
(0~10)mA | |||
(0~100)mV | ±0.2 | ||
(-20~20)mV | |||
(0~20)mV | |||
Thermocouple Input (Without Cold Junction Error) | |||
Signal type | Measuring range (°C) | Maximum allowable error (°C) | |
B | 600 ~ 1800 | ±2.4 | |
E | -200 ~ 1000 | ±2.4 | |
J | -200 ~ 1200 | ±2.4 | |
K | -200 ~ -100 | ±3.3 | |
-100 ~ 1300 | ±2.0 | ||
S | -50 ~ 100 | ±3.7 | |
100 ~ 300 | ±2.0 | ||
300 ~ 1600 | ±1.5 | ||
T | -200 ~ -100 | ±1.9 | |
-100 ~ 400 | ±1.6 | ||
R | -50 ~ 100 | ±3.7 | |
100 ~ 300 | ±2.0 | ||
300 ~ 1600 | ±1.5 | ||
N | -200 ~ 1300 | ±3.0 | |
WRe5-26 | 0~ 2310 | ±4.0 | |
WRe3-25 | 0~ 2315 | ±4.0 | |
RTD Input | |||
Signal type | Measuring range (°C) | Maximum allowable error (°C) | |
Cu50 | -50 ~ 150 | ±1.0 | |
Pt100 | -200 ~ 650 | ±1.0 | |
Pt1000 | -200 ~ 200 | ±1.0 | |
Note: special type thermal resistance can be customized. |
Output Signal | ||||||
Alarm Output | ||||||
Signal type | Measuring range | Contact type | Contact rating | Response cycle | ||
Alarm Output | 0/1 | Normally open contact | 2A /250VAC | 1 second | ||
Current Output | ||||||
Signal type | Range (mA) | Maximum allowable error (mA) |